Inspection visit

Fire Safety inspection

Luther HomeCMS #52547615 citations on this visit
15 citations recorded

Citations

15 citations recorded*CMS

This is a Fire Safety survey. CMS cites these findings under the Life Safety Code and Emergency Preparedness rules, a separate set from the health (F-tag) deficiencies. The codes and grading differ, so these do not link to the health violation pages.

What do CMS severity letters mean?

Serious (G-L). Actual harm to a resident, or immediate jeopardy. Codes G through I indicate actual harm; J through L indicate immediate jeopardy to resident health or safety.

General (A-F). No actual harm found, or harm that is minimal. The facility must still submit a Plan of Correction. Most CMS citations land here.

Each letter combines severity with scope: how many residents the deficiency affected.

  • 0345GeneralS&S Fpotential for harm

    Have approved installation, maintenance and testing program for fire alarm systems.

  • 0362GeneralS&S Fpotential for harm

    Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke.

  • 0363GeneralS&S Dpotential for harm

    Install corridor and hallway doors that block smoke.

  • 0374GeneralS&S Epotential for harm

    Install smoke barrier doors that can resist smoke for at least 20 minutes.

  • 0511GeneralS&S Epotential for harm

    Have properly installed electrical wiring and gas equipment.

  • 0521GeneralS&S Dpotential for harm

    Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

  • 0711GeneralS&S Fpotential for harm

    Provide a written emergency evacuation plan.

  • 0712GeneralS&S Cno actual harm

    Have simulated fire drills held at unexpected times.

  • 0911GeneralS&S Fpotential for harm

    Meet requirements for the installation and maintenance of electrical systems.

  • 0032GeneralS&S Fpotential for harm

    Provide primary/alternate means for communication.

  • 0039GeneralS&S Fpotential for harm

    Conduct testing and exercise requirements.

  • 0321GeneralS&S Fpotential for harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

  • 0341GeneralS&S Fpotential for harm

    Install a fire alarm system that can be heard throughout the facility.

  • 0031GeneralS&S Fpotential for harm

    Provide emergency officials' contact information.

  • 0353GeneralS&S Fpotential for harm

    Inspect, test, and maintain automatic sprinkler systems.

FAQ · About this visit

Common questions about this visit

What happened during the June 7, 2023 survey of Luther Home?

This was a inspection survey of Luther Home on June 7, 2023. The surveyor cited 15 deficiencies, recorded on the federal Form 2567 statement of deficiencies.

Were any deficiencies cited at Luther Home on June 7, 2023?

Yes, 15 deficiencies were cited, each with a CMS Scope and Severity grade. The first was: "Have approved installation, maintenance and testing program for fire alarm systems."

What type of survey was this?

This was a inspection survey conducted by state surveyors under federal Centers for Medicare & Medicaid Services (CMS) oversight. Findings are published on CMS Care Compare.

Share this reportEmail

Next steps

Concerned about a resident’s care?Find your local ombudsman through the Eldercare Locatoror file a complaint with your state survey agency.

Researching this visit professionally?Book a 15-minute calland we will walk through what we have on file.

Data from CMS Care Compare public records. Dataset last refreshed . If you believe any information is inaccurate, report it here.