Inspection visit
Fire Safety inspection
Citations
15 citations recorded*CMS
This is a Fire Safety survey. CMS cites these findings under the Life Safety Code and Emergency Preparedness rules, a separate set from the health (F-tag) deficiencies. The codes and grading differ, so these do not link to the health violation pages.
What do CMS severity letters mean?
Serious (G-L). Actual harm to a resident, or immediate jeopardy. Codes G through I indicate actual harm; J through L indicate immediate jeopardy to resident health or safety.
General (A-F). No actual harm found, or harm that is minimal. The facility must still submit a Plan of Correction. Most CMS citations land here.
Each letter combines severity with scope: how many residents the deficiency affected.
- 0223GeneralS&S Dpotential for harm
Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.
- 0271GeneralS&S Dpotential for harm
Have exits that are accessible at all times.
- 0321GeneralS&S Dpotential for harm
Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.
- 0324GeneralS&S Dpotential for harm
Provide properly protected cooking facilities.
- 0345GeneralS&S Dpotential for harm
Have approved installation, maintenance and testing program for fire alarm systems.
- 0353GeneralS&S Fpotential for harm
Inspect, test, and maintain automatic sprinkler systems.
- 0355GeneralS&S Dpotential for harm
Properly select, install, inspect, or maintain portable fire extinguishes.
- 0761GeneralS&S Fpotential for harm
To conduct inspection, testing and maintenance of fire doors by qualified individuals.
- 0781GeneralS&S Dpotential for harm
Have restrictions on the use of portable space heaters.
- 0918GeneralS&S Fpotential for harm
Have generator or other power source capable of supplying service within 10 seconds.
- 0920GeneralS&S Dpotential for harm
Ensure proper usage of power strips and extension cords.
- 0222GeneralS&S Dpotential for harm
Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.
- 0712GeneralS&S Fpotential for harm
Have simulated fire drills held at unexpected times.
- 0031GeneralS&S Fpotential for harm
Provide emergency officials' contact information.
- 0041GeneralS&S Fpotential for harm
Implement emergency and standby power systems.
FAQ · About this visit
Common questions about this visit
What happened during the November 18, 2025 survey of Life Care Center of Cheyenne?
This was a inspection survey of Life Care Center of Cheyenne on November 18, 2025. The surveyor cited 15 deficiencies, recorded on the federal Form 2567 statement of deficiencies.
Were any deficiencies cited at Life Care Center of Cheyenne on November 18, 2025?
Yes, 15 deficiencies were cited, each with a CMS Scope and Severity grade. The first was: "Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smok..."
What type of survey was this?
This was a inspection survey conducted by state surveyors under federal Centers for Medicare & Medicaid Services (CMS) oversight. Findings are published on CMS Care Compare.
SourceView on CMS Care Compare