Inspection visit
Fire Safety inspection
Citations
17 citations recorded*CMS
This is a Fire Safety survey. CMS cites these findings under the Life Safety Code and Emergency Preparedness rules, a separate set from the health (F-tag) deficiencies. The codes and grading differ, so these do not link to the health violation pages.
What do CMS severity letters mean?
Serious (G-L). Actual harm to a resident, or immediate jeopardy. Codes G through I indicate actual harm; J through L indicate immediate jeopardy to resident health or safety.
General (A-F). No actual harm found, or harm that is minimal. The facility must still submit a Plan of Correction. Most CMS citations land here.
Each letter combines severity with scope: how many residents the deficiency affected.
- 0039GeneralS&S Fpotential for harm
Conduct testing and exercise requirements.
- 0291GeneralS&S Cno actual harm
Install emergency lighting that can last at least 1 1/2 hours.
- 0293GeneralS&S Cno actual harm
Have properly located and lighted "Exit" signs.
- 0345GeneralS&S Fpotential for harm
Have approved installation, maintenance and testing program for fire alarm systems.
- 0346GeneralS&S Cno actual harm
Follow proper procedures when the fire alarm was out of service for more than 4 hours.
- 0352GeneralS&S Fpotential for harm
Properly install and monitor supervisory attachments on automatic sprinkler systems.
- 0353GeneralS&S Fpotential for harm
Inspect, test, and maintain automatic sprinkler systems.
- 0354GeneralS&S Cno actual harm
Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.
- 0355GeneralS&S Dpotential for harm
Properly select, install, inspect, or maintain portable fire extinguishes.
- 0363GeneralS&S Epotential for harm
Install corridor and hallway doors that block smoke.
- 0374GeneralS&S Epotential for harm
Install smoke barrier doors that can resist smoke for at least 20 minutes.
- 0521GeneralS&S Fpotential for harm
Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.
- 0712GeneralS&S Cno actual harm
Have simulated fire drills held at unexpected times.
- 0781GeneralS&S Dpotential for harm
Have restrictions on the use of portable space heaters.
- 0918GeneralS&S Dpotential for harm
Have generator or other power source capable of supplying service within 10 seconds.
- 0919GeneralS&S Dpotential for harm
Meet requirements for the use of electrical equipment.
- 0920GeneralS&S Dpotential for harm
Ensure proper usage of power strips and extension cords.
FAQ · About this visit
Common questions about this visit
What happened during the January 24, 2025 survey of ARBOR POST ACUTE?
This was a inspection survey of ARBOR POST ACUTE on January 24, 2025. The surveyor cited 17 deficiencies, recorded on the federal Form 2567 statement of deficiencies.
Were any deficiencies cited at ARBOR POST ACUTE on January 24, 2025?
Yes, 17 deficiencies were cited, each with a CMS Scope and Severity grade. The first was: "Conduct testing and exercise requirements."
What type of survey was this?
This was a inspection survey conducted by state surveyors under federal Centers for Medicare & Medicaid Services (CMS) oversight. Findings are published on CMS Care Compare.