Inspection visit
Fire Safety inspection
Citations
20 citations recorded*CMS
This is a Fire Safety survey. CMS cites these findings under the Life Safety Code and Emergency Preparedness rules, a separate set from the health (F-tag) deficiencies. The codes and grading differ, so these do not link to the health violation pages.
What do CMS severity letters mean?
Serious (G-L). Actual harm to a resident, or immediate jeopardy. Codes G through I indicate actual harm; J through L indicate immediate jeopardy to resident health or safety.
General (A-F). No actual harm found, or harm that is minimal. The facility must still submit a Plan of Correction. Most CMS citations land here.
Each letter combines severity with scope: how many residents the deficiency affected.
- 0004GeneralS&S Epotential for harm
Develop and maintain an Emergency Preparedness Program (EP).
- 0006GeneralS&S Dpotential for harm
Conduct risk assessment and an All-Hazards approach.
- 0161GeneralS&S Dpotential for harm
Use approved construction type or materials.
- 0225GeneralS&S Epotential for harm
Have stairways and smokeproof enclosures used as exits that meet safety requirements.
- 0291GeneralS&S Epotential for harm
Install emergency lighting that can last at least 1 1/2 hours.
- 0293GeneralS&S Epotential for harm
Have properly located and lighted "Exit" signs.
- 0324GeneralS&S Epotential for harm
Provide properly protected cooking facilities.
- 0341GeneralS&S Epotential for harm
Install a fire alarm system that can be heard throughout the facility.
- 0345GeneralS&S Fpotential for harm
Have approved installation, maintenance and testing program for fire alarm systems.
- 0346GeneralS&S Epotential for harm
Follow proper procedures when the fire alarm was out of service for more than 4 hours.
- 0352GeneralS&S Fpotential for harm
Properly install and monitor supervisory attachments on automatic sprinkler systems.
- 0353GeneralS&S Epotential for harm
Inspect, test, and maintain automatic sprinkler systems.
- 0355GeneralS&S Epotential for harm
Properly select, install, inspect, or maintain portable fire extinguishes.
- 0363GeneralS&S Dpotential for harm
Install corridor and hallway doors that block smoke.
- 0531GeneralS&S Epotential for harm
Have elevators that firefighters can control in the event of a fire.
- 0918GeneralS&S Epotential for harm
Have generator or other power source capable of supplying service within 10 seconds.
- 0919GeneralS&S Epotential for harm
Meet requirements for the use of electrical equipment.
- 0923GeneralS&S Epotential for harm
Have proper medical gas storage and administration areas.
- 0926GeneralS&S Epotential for harm
Ensure that personnel concerned with handling of medical gases and cylinders are trained on the risk.
- 0344GeneralS&S Dpotential for harm
Have an alternate power supply for its alarm system.
FAQ · About this visit
Common questions about this visit
What happened during the November 4, 2021 survey of OAKLAND HEIGHTS NURSING AND REHABILITATION?
This was a inspection survey of OAKLAND HEIGHTS NURSING AND REHABILITATION on November 4, 2021. The surveyor cited 20 deficiencies, recorded on the federal Form 2567 statement of deficiencies.
Were any deficiencies cited at OAKLAND HEIGHTS NURSING AND REHABILITATION on November 4, 2021?
Yes, 20 deficiencies were cited, each with a CMS Scope and Severity grade. The first was: "Develop and maintain an Emergency Preparedness Program (EP)."
What type of survey was this?
This was a inspection survey conducted by state surveyors under federal Centers for Medicare & Medicaid Services (CMS) oversight. Findings are published on CMS Care Compare.