Inspection visit
Fire Safety inspection
Citations
14 citations recorded*CMS
This is a Fire Safety survey. CMS cites these findings under the Life Safety Code and Emergency Preparedness rules, a separate set from the health (F-tag) deficiencies. The codes and grading differ, so these do not link to the health violation pages.
What do CMS severity letters mean?
Serious (G-L). Actual harm to a resident, or immediate jeopardy. Codes G through I indicate actual harm; J through L indicate immediate jeopardy to resident health or safety.
General (A-F). No actual harm found, or harm that is minimal. The facility must still submit a Plan of Correction. Most CMS citations land here.
Each letter combines severity with scope: how many residents the deficiency affected.
- 0039GeneralS&S Fpotential for harm
Conduct testing and exercise requirements.
- 0222GeneralS&S Epotential for harm
Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.
- 0223GeneralS&S Epotential for harm
Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.
- 0293GeneralS&S Fpotential for harm
Have properly located and lighted "Exit" signs.
- 0321GeneralS&S Epotential for harm
Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.
- 0324GeneralS&S Fpotential for harm
Provide properly protected cooking facilities.
- 0342GeneralS&S Epotential for harm
Have a complete alarm system manually initiated and initiated by fire sprinkler system connection.
- 0353GeneralS&S Fpotential for harm
Inspect, test, and maintain automatic sprinkler systems.
- 0372GeneralS&S Epotential for harm
Ensure smoke barriers are constructed to a 1 hour fire resistance rating.
- 0374GeneralS&S Fpotential for harm
Install smoke barrier doors that can resist smoke for at least 20 minutes.
- 0511GeneralS&S Fpotential for harm
Have properly installed electrical wiring and gas equipment.
- 0741GeneralS&S Fpotential for harm
Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.
- 0761GeneralS&S Fpotential for harm
To conduct inspection, testing and maintenance of fire doors by qualified individuals.
- 0918GeneralS&S Fpotential for harm
Have generator or other power source capable of supplying service within 10 seconds.
FAQ · About this visit
Common questions about this visit
What happened during the August 8, 2024 survey of Southern Oaks Therapy and Living Center?
This was a inspection survey of Southern Oaks Therapy and Living Center on August 8, 2024. The surveyor cited 14 deficiencies, recorded on the federal Form 2567 statement of deficiencies.
Were any deficiencies cited at Southern Oaks Therapy and Living Center on August 8, 2024?
Yes, 14 deficiencies were cited, each with a CMS Scope and Severity grade. The first was: "Conduct testing and exercise requirements."
What type of survey was this?
This was a inspection survey conducted by state surveyors under federal Centers for Medicare & Medicaid Services (CMS) oversight. Findings are published on CMS Care Compare.